MERCEDES-BENZ, MERCEDES-MAYBACH
LI83.30-P-079081
2025-04-21 · NHTSA 11017217
إدراج السيارة هو نقطة بداية للبحث. تحقق من المحرك وفترة الإنتاج والبرمجيات في معلومات الشركة المصنعة.
ملخص الشركة
النص الأصلي بالإنجليزية
Complaint Random heating of air conditioning system. Cause Temperature sensor in overhead control panel (OCP) delivering incorrect values: The temperature sensor in the overhead control panel is malfunctioning. Fault code B110709 or fault code B11F697 are present in the overhead control panel with the status (active) or (active stored). or The temperature sensor in the overhead control panel measures an incorrect temperature (the temperature value can be checked against the actual value in the overhead control panel) If the above-mentioned fault code is not present, the cause could be malfunction on the air conditioning system. Remedy If one of the above-mentioned fault codes should occur, a TIPS case must be created here. If the above fault codes or actual value differences are present in the OCP - please send the case to the Body/Chassis/ Entertainment inbox. Otherwise, the case must be sent to the HV/LV inbox for support in A/C diagnosis. *** It is not necessary to replace the overhead control panel ***